High Accuracy CT PT Transformer Parameter Analyzer
Introduction:High Accuracy CT PT Transformer Parameter Analyzer is an all in one solution for testing all type of CT/PT ;
Basic Info
Model NO. | GDVA-405 |
Voltage Output | 0.1~180V (AC) |
Current Output | 0.001~5A (RMS) |
Power Output | 500va |
Maximum Knee Voltage | 60kv |
Current Measurement Range | 0~10A |
Secondary Current | 1A,3A,5A |
Transport Package | Wooden Case |
Specification | 49*19*36CM |
Trademark | Gold |
Origin | Chongqing |
HS Code | 9031809090 |
Production Capacity | 200PCS/Month |
Product Description
Introduction:High Accuracy CT PT Transformer Parameter Analyzer is an all in one solution for testing all type of CT/PT as per IEC standards. It is an equipment with high return on investment. Below features make CT PT Parameter Analyzer an ideal choice for measuring current transformers and potential transformers:
Low Testing Time (Completes all test for CT/PT Winding & Cores in a few min)
Simple connection (Simple one time connection)
Highest Accuracy (0.02% for typical, 0.1% for guaranteed)
Portable & Light Weight
High Interference Rejection (Can be used in 220/400/765 KV Live Switchyards )
Specifications:
GDVA-405 High Accuracy CT PT Transformer Parameter Analyzer | ||
1 | Test standards | IEC60044-1, IEC60044-2, IEC60044-5, IEC60044-6, IEC61869 and C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~180V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 500VA |
6 | Max. knee voltage measurement | 60kv |
7 | Current measurement range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
8 | Current measurement error | <±0.1%+0.01%FS |
9 | Voltage measurement range | 0~200 V (automatically change range in 1V/10V/70V/200V) |
10 | Voltage measurement error | < ±0.1%+0.01%FS |
11 | Turns ratio measurement range | 1~30000;1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 | Phase measurement | error:±2min,resolution:0.01min |
13 | Coil resistance measurement | Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
15 | CT Secondary burden | Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 | PT Secondary burden | Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 | PT ratio measurement | Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5% |
18 | Saved data groups | >1000groups |
19 | Work condition | Temperature:-10ºC-50ºC, moist:≤90% |
20 | Size | 49*19*36CM |
21 | Weight | 15kg |
Applications:
Current transformer analyzer is used for various types of CT (such as protection, metering, TP) excitation characteristics (volt-ampere characteristics), ratio, polarity, secondary winding resistance, quadratic compliance, ratio difference and angular difference Wait for test requirements.